Reverse Osmosis Scale Inhibitors: A Comprehensive Guide
1. Calculation of Reverse Osmosis Antiscalants:
Reverse osmosis scale inhibitors are commonly available in standard solutions or concentrated forms (such as 4x, 8x, and 11x concentrates). The primary reason for offering concentrated versions is to reduce packaging and shipping costs. By increasing the product concentration, importers or distributors can resell it either as a ready-to-use solution or dilute it before sale.
The recommended dosage for reverse osmosis antiscalants typically ranges from 3 to 6 ppm, which translates to 3 to 6 grams of inhibitor per ton of water processed. To calculate the monthly usage, the following formula is used:
**W = Q × S × H × 30 / 1000**
Where:
- **W** = Monthly dosage (in kg)
- **Q** = Feed flow rate (in m³/h)
- **S** = Dosage concentration (in ppm or g/ton)
- **H** = Operating hours per day
- **30** = Number of days in a month
- **1000** = Conversion factor from grams to kilograms
For example, if an RO plant produces 75 tons of water per hour, the feed water volume would need to be at least 100 tons per hour. Using a dosage of 3.5 ppm, the monthly consumption would be:
**100 × 3.5 × 24 × 30 / 1000 = 252 kg**
This calculation ensures that the system receives the correct amount of inhibitor to prevent scaling and maintain optimal performance.
2. Application of Reverse Osmosis Scale Inhibitors:
Scale inhibitors are typically added to the reverse osmosis system through a dosing pump, usually after the security filter or precision filter. They can be applied directly or diluted, but the dilution ratio should not exceed 10 times. This means the diluted concentration should not fall below 10% of the original strength.
It's important to use a clean and properly sealed dosing system to avoid contamination. The injection point should be carefully selected to ensure even distribution throughout the feed water stream.
3. Key Considerations for Using Reverse Osmosis Antiscalants:
- Always ensure the dosing system is clean and sealed before each operation.
- It's best to use the inhibitor within the recommended shelf life to maintain effectiveness.
- When diluting, always use high-quality purified water to avoid introducing impurities into the system.
- Regular monitoring of the dosing system and chemical levels is essential to prevent under or over-dosing.
- Keep records of the dosing schedule and adjust based on changes in feed water quality or system performance.
By following these guidelines, operators can maximize the efficiency of their reverse osmosis systems and extend the lifespan of membranes while minimizing maintenance costs.